Performance Estimation of Heat Exchanger Operates By Evaporative Cooling Manner

Authors

  • Imaad Sedeeq Mohammed Department of Engineering/ University of Technology
  • Salah Karem Juaad Department of Engineering/ University of Technology

Abstract

        In this study the design and installation of evaporative air cooler was carried out using completely outdoor air (fresh air) according to two stage evaporative cooling principle. The laboratory equipment was installed by designing and manufacturing a cross flow plate heat exchanger, where aluminum plates used for this purpose with dimensions (50 × 30 × 40 cm). The surfaces of heat exchanger were covered by sawdust from wetted channels side, to increase the percentage of wetting these surfaces and hence improve the performance and efficiency of air cooler.

        An experimental study was carried out to estimate the performance of cooling system, where some of the dominant effective parameters were studied like air flow rate and flow rate and effect the static pressure drop of air and the heat transfer of performance .Air flow rate was ranged between (142.90 to 1461.50 m3 / hr) and water flow rate was varied from (144 L / hr) to (1050 L / hr).

        The experimental results showed that the optimum flow rate of air prepared by the air cooler is (824.7 m3 / hr), As it to be seen from the study that treating the heat exchanger surfaces by sawdust improves the air cooler efficiency about (10 %), but in the other hand leads to increase the static pressure drop in proportion (21%) approximately, and hence increase consumed power about (9 %).The results also show the air cooler can not be used in regions that have moisture content accedes (11.90 g moisture/kg dry air).

 

Downloads

Download data is not yet available.

References

[1] Gonzales , D.J. ; " The Scince and Application of Evaporative Cooling " , American Industrial Hygiene Association Journal , Vol.27,March – April 1966 , PP. 172 – 179 .
[2] Kennedy , R.A. " A Two-Stage Evaporative Coolers " M.Sc. Thesis , University of Texas , Austin , Tex. , May 1953 , PP. 32 – 38 .
[3] شمعون , دونال جبرائيل " التبريد التبخيري لتكييف الهواء على مرحلتين " رسالة ماجستير , الجامعة التكنولوجية , أيلول 1989 .
[4] CHAN , C.Y.L. ; "Performance Test of Model Plate Heat Exchanger With Wetted Plates " CSIRO Division of Mechanical Engineering , Internal Report No.120 Victoria , Australia , March 1973 , PP. 1 – 6 .
[5] مرتضى , طالب كشاش " دراسة عملية عن إمكانية زيادة كفاءة مبردات الهواء التجارية المباشرة " رسالة دبلوم عالي , الجامعة التكنولوجية , آذار 1980 .
[6] AL – Khatib , A.M.J. " An Investigation in to The Effect of Precooling Water on The Performance of Evaporative Air Cooling " M.S.c Thesis , University of Baghdad , January 1984 .
[7] PESCOD , D. , " Unit Air Cooler Using Plastic Heat Exchanger With Evaporatively Cooled Plates " Australian Refrigeration , Air Conditioning and Heating , Vol.22 , No.9 , Sept. 1968 , PP. 22 – 26
[8] PESCOD , D. , " Effect of Turbulance Promoters on The Performance of Plate Heat Exchangers " Heat Exchangers : Design & Theory Sourcebook , Mc Graw – Hill , New York , 1974 , CH. 22 , PP. 601 – 615 .
[9] IHVE Guide " Flow of Fluids in Pipes and Ducts " , CH.4 , 49 Cadogan Square Loud SWLXOJB,1977.